ATEX
Operators instructions
CleverLevel switch, LFFS
Ex ia IIC T5, ATEX II 1G - Installation
A Level Switch LFFS-1xx.x is Ex ia IIC T5, ATEX II 1G ap-
proved for application in hazardous areas in accordance with
the current EU directives. The product must be installed in
accordance with prevailing guidelines for zone 0 with a barrier
Ex-data
Supply range 24...30 VDC
Temperature class T1...T5 Pls. see above table
Internal inductivity L
i
<10 µH
Internal capacity C
i
<33 nF
Barrier data U <30 VDC
I <0.1 A
P <0.75 W
Connection type Ambient temperature Media temperature
(max. allowed)
Note
G½ hygienic -40 … +85 °C +85 °C
3A DN38
-40 … +60 °C +95 °C 1)
-40 … +40 °C +115 °C 1)
100 mm -40 … +85 °C +85 °C
Sliding connection
-40 … +60 °C +155 °C 1)
-40 … +40 °C +175 °C 1)
250 mm -40 … +85 °C +85 °C
Sliding connection
-40 … +60 °C +195 °C 1)
-40 … +40 °C +200 °C 1)
Conditions for Ex certification
1) Provided that
the sensor tip
at the instru-
ment is the
only part in
contact with
the media
ATEX Gas ia
LFFS-1xx.x
with PNP output
Safe area
+ 22...120 VDC
or
- 90...253 VAC
Note:
For PNP output the barrier module
PFOFSI3-B25100-ALG-LS
is required for functional purposes.
PFOFSI3-B25100-ALG-LS
NPN out
LFFS-1xx.x
with NPN output
Note:
For NPN output only!
A standard barrier may be used
Standard barrier
Two-channel
ZENER barrier
www.baumer.com Operators instructions: 11109132 02 EN Page 8 / 12
Note:
There is an electrical connection between intrinsic safe circuit
and housing due to the measurement principle